Bus duct
| Electrical installations |
|---|
| Wiring practice by region or country |
| Regulation of electrical installations |
| Cabling and accessories |
| Switching and protection devices |

In electric power distribution, a bus duct (also called busway) typically uses sheet metal, welded metal[1] or cast resin to contain and isolate copper or aluminium busbars for the purpose of conducting a substantial current of electricity. It is an alternative means of conducting electricity to power cables or cable bus.
Originally a busway consisted of bare copper conductors supported on inorganic insulators, such as porcelain, mounted within a non-ventilated steel housing.[2]
History
Busways were produced due to request of the automotive industry in Detroit in the late 1920s. Since that time, busways improved and became an integrated part of secondary network for industrial plants.[2]
Construction
-
Section of aluminium bus duct with sandwiched bus bars
-
Individual busbar wrapping
-
Bus duct, also called busway, is available with (3) finger-safe #8AWG copper wires in steel housing.
Some bus ducts are rectangular similar to cable tray, but have thicker, cold-formed steel side rails and thinner sheet metal coverings. Others can be circular.[3] Busbars inside may be separated with distinct and even gaps between them, or “sandwiched” together.
Typically, individual busbars are wrapped or coated with a non-conducting, covalent material, such as plastic or (in older systems) electrical tape.
The structural integrity and electrical efficiency of these interleaved busbars depend heavily on the precision of cutting, punching, and bending processes. Advanced CNC busbar processing technology is increasingly utilized to ensure that connection points are perfectly aligned, thereby minimizing power loss and preventing overheating.[4]
At the connection point, busbars flare out to enable connection to the next segment.
A plug-in bus duct system or busway can have disconnect switches and other devices mounted on it, for example, to distribute power along a long building. Many forms of busway allow plug-in devices such as switches and motor starters to be easily moved; this provides flexibility for changes on an assembly line, for example.[5] In addition to powering floor fixtures, busways can provide power to plug-in light fixtures and even IoT devices.[6]
Feeder busway is used to interconnect equipment, such as between a transformer and a switchgear line up. A variant type is a low-impedance busway, which is designed to have lower voltage drop by virtue of close spacing of bus bars, which reduces inductive reactance.
A trolley busway provides power to equipment that must be frequently moved. The busway is open at the bottom, and a movable collector assembly "trolley" is used to connect between the fixed bus bars in the busway and the cable connected to moving equipment.[5] Bus ducts are building service penetrants that are required to be externally firestopped where they penetrate fire separations required to have a fire-resistance rating.
See also
References
- ^ "Isolated Phase Bus Duct". Stace. Retrieved 2024-01-04.
- ^ a b "IEEE 3001.5-2013 - IEEE Recommended Practice for the Application of Power Distribution Apparatus in Industrial and Commercial Power Systems". The IEEE Standards Association. 2013-12-11. Archived from the original on April 12, 2014. Retrieved 2018-01-09.
- ^ "Isolated Phase Bus Duct". Stace. Retrieved 2024-01-04.
- ^ zhang, Mike (2026-05-06). "CNC Busbar Processing Technology". LTMC Machinery. Retrieved 2026-05-06.
{{cite web}}: CS1 maint: url-status (link) - ^ a b Terrel Croft, Wilford Summers (ed)American Electricians Handbook Eleventh Edition, McGraw-Hill 1987, ISBN 0-07013932-6, pages 9-114 through 9-132
- ^ "Why busSTRUT". busSTRUT. Retrieved 2024-01-13.
External links
- Merriam Webster Definition of Bus Duct
- *Bus Duct Construction and Installation on YouTube
- Underwriters Laboratories Standard UL857 abstract
- IEEE C37.23 Standard For Metal Enclosed Bus
- Interpretations for IEEE Std C37.23-1987 IEEE Guide for Metal-Enclosed Bus and Calculating Losses in Isolated-Phase Bus
- IEEE P3004.7 - Recommended Practice for the Protection of Power Cables and Busway Used in Industrial and Commercial Power Systems
- IEEE Busway Short Circuit Testing Procedures
- IEEE Mathematical model of high voltage sandwich bus duct
Content Disclaimer
Informasi ini disarikan dari Wikipedia dan disajikan kembali untuk tujuan edukasi. Konten tersedia di bawah lisensi CC BY-SA 3.0. Kami tidak bertanggung jawab atas ketidakakuratan data yang bersumber dari kontribusi publik tersebut.
- The information displayed on this website is sourced in part or in whole from Wikipedia and has been adapted for the purpose of restating it. We strive to provide accurate and relevant information, however:
- There is no guarantee of absolute accuracy. Wikipedia is an open, collaborative project that can be edited by anyone, so information is subject to change.
- It is not intended to constitute professional advice. The content displayed is for informational and educational purposes only. For important decisions (e.g., medical, legal, or financial), please consult a professional.
- Content copyright. Wikipedia is licensed under the Creative Commons Attribution-ShareAlike License (CC BY-SA). This means that content may be reused with appropriate attribution and shared under a similar license.
- Responsible use. Any risk arising from the use of information from this website is entirely the responsibility of the user.